Network Emissions (O_network)

In short: O_network is the carbon from the electricity used to carry your application's data from the data centre to the user's device. It is optional: the headline score always leaves it out, and you may report a second, labelled score that includes it when you can quantify it defensibly. This page explains how to quantify it, where the line with server energy falls, and how to avoid counting the same energy twice.

Shape: network energy attributable to the application × grid carbon intensity = network emissions.

Worked: 80 kWh × 250 gCO2eq/kWh = 20 kg CO2eq for the month. (illustrative placeholder, not a real measurement)

Precise notation:

O_network = E_network × I_network

from the data centre's facility exit to the network interface of the user's device (Clause 3.3).

Why it is optional​

Measuring network electricity defensibly is hard, and the most common estimates rely on bytes transferred, an acknowledged weak proxy. The Formula Walkthrough gives the full rationale. Optional means optional for every team, whatever its data maturity: no implementation tier implies that O_network is expected. Whether two-score reporting should stay is Open Question 3.

Choosing a method​

Where O_network is reported, Clause 7.3 requires the most direct available method, in this order:

  1. Direct measurement: measured energy for the traffic attributable to your application, for example from an ISP or CDN partner that supplies measured energy data.
  2. Hybrid model: measured or supplier-disclosed energy for some network segments (such as a last-mile operator's energy reports), with the remainder modelled. We recommend disclosing which segments are measured and which modelled, and the rationale for each modelling coefficient.
  3. Data-transfer model: a model based on data transferred, such as the Sustainable Web Design Model (SWDM) or CO2.js coefficients, used only where neither of the above is available.

Clause 7.3 requires you to disclose the method used and why a more direct one was not used. When you fall back to a data-transfer model, we also recommend disclosing the model and coefficients, that bytes transferred is an acknowledged weak proxy for network energy, and that the result carries high methodological uncertainty.

(Named models and tools on this page last reviewed: 2026-10. See the Tools Directory.)

Measuring data transfer​

When a data-transfer model is used, a common approach is to count all bytes exchanged between server infrastructure and end-user devices:

  • HTML, CSS, JavaScript, images, video and fonts;
  • API responses and request bodies;
  • WebSocket and other real-time protocol traffic;
  • HTTP headers and protocol overhead.

Measure at the application layer, after compression: the bytes that actually crossed the network, not the uncompressed size of the assets.

Do not present byte savings as network savings​

Clause 7.3 recommends that reductions in O_network estimated solely from data transferred are not presented as evidence of emission reductions. Fewer bytes can mean no less network energy: edge caching, for example, shifts energy rather than eliminating it. If you shrink your pages, report the change, but lead with the components where the saving is real, such as O_client and O_server.

CDN and edge energy: where it belongs​

Clause 5.5 sets the line between O_server and O_network at data-centre facility egress, and attributes CDN and edge energy by how it was measured, not by what kind of service it is:

  1. Measured as facility energy (an edge data centre with a PUE, metered infrastructure) → O_server.
  2. Allocated on a transmission basis (traffic-based, SWDM-style allocation) → O_network.
  3. Bundled by the supplier without a clear split → Clause 5.5 requires you to disclose how you divided it between components.

For a bundled figure, we recommend recording which components received a portion, the rationale for the split, and the assumptions about measurement regime that justify it. Clause 5.5 also says energy is never counted in more than one component.

Example: splitting a bundled CDN figure​

A CDN provider publishes a single figure: "CDN total energy for your traffic = 42 kWh/month". The application uses the CDN for static assets and edge functions. Using the CDN's analytics, the team finds that 70 % of requests are cache hits served without origin compute. It allocates 70 % of the 42 kWh (29.4 kWh) to O_network as transmission, and 30 % (12.6 kWh) to O_server as edge compute. It discloses the allocation rule, the source of the ratio, and that it will switch to component-specific figures if the CDN publishes them. (illustrative placeholder, not a real measurement) A template for this disclosure is on Implementation Templates.

The split is not score-neutral when O_network is omitted​

That 70/30 split moves 29.4 kWh into O_network. If the team then reports only the headline score, which leaves O_network out, those 29.4 kWh vanish from the reported score even though the energy was used. That is energy displacement: shifting energy from a measured component to an unmeasured one. Clause 10 states that energy displacement does not reduce the score.

So when O_network is not reported, any bundled CDN energy allocated on a transmission basis is excluded from the score, and should be named, with its quantity, in the limitations disclosure (Clause 8 item 11), next to the allocation disclosure Clause 5.5 requires. Do not present the split as score-neutral. How the specification should treat this case is Open Question 4.

Weighting by connection type​

Mobile radio access networks generally use substantially more energy per bit than fixed connections such as fibre, with the difference varying by network and generation. Default SWDM coefficients are blended averages across connection types.

Where you use a data-transfer model and know your users' connection mix (for example from analytics), we recommend weighting the calculation by connection type. Weighting is good practice, not a requirement, and we recommend stating whether you applied it.

Using SWDM without double counting​

SWDM divides a single system energy total across data centres, networks and devices. If you take its network segment for O_network and also measure O_server and O_client directly, using SWDM's data-centre and device segments as well would count the same energy twice.

When using SWDM for O_network:

  • use only its network segment;
  • discard its data-centre and device segments, replacing them with your direct measurement of O_server and O_client;
  • disclose the SWDM version and coefficients, whether connection-type weighting was applied, how edge facility energy was handled, and known limitations. Clause 8 item 5 requires the models and coefficients used to be disclosed; the rest is recommended practice.

Please submit any comments you have here.